Engine Governing

The PowerCommand control includes integrated digital governing capability, to directly drive an engine fuel control valve. Features of the governing system (when enabled) include:

Isochronous Governing - Controls engine speed within plus or minus 0.25% for any steady state load from no load to full load. Frequency drift will not

exceed plus or minus 0.5% for a 60F (33C) change in ambient temperature over an 8 hour period.

Temperature Dynamics - Modifies the engine fuel system (governing) control parameters as a function of engine temperature. Allows engine to be more responsive when warm, and more stable when operating at lower temperature levels.

Idle Mode – The control system accepts a signal to control engine speed to a preset, adjustable idle speed when operating in the RUN mode.

Protective Functions

On a warning condition the control will indicate a fault by lighting the warning LED on the control panel, and displaying the fault name and code on the operator display panel. The nature of the fault and time of occurrence are logged in the control. The service manual and InPower service tool provide service keys and procedures based on the service codes provided. On a shutdown condition, the control will light the shutdown LED on the control panel, display the fault name and code, and initiate shut down and lock out the generator set. The control maintains a data log of all fault conditions as they occur, and time stamps them with the engine operating hours data.

Some protective functions within the control system are configurable for warning, or shutdown. PowerCommand provides the following system protective functions:

§ Ground Fault Warning (option- 600VAC class

generator sets with solid ground) - Ground fault sensing is adjustable over a range of 100-1200 amps, with time delays of 0-1 second. May be configured for shutdown rather than alarm. § Configurable Alarm And Status Inputs -PowerCommand will accept up to four alarm or status inputs (configurable contact closed to ground or open) to indicate customer-specified conditions. The control is programmable for warning or shutdown, and for labeling the input. § Emergency Stop - Annunciated whenever the

local or remote emergency stop signal is received. Alarm panel distinguishes between local or remote operation.

Alternator Control

PowerCommand includes an integrated 3-phase line-to-neutral sensing voltage regulation system that is compatible with either shunt or PMG type excitation systems. The voltage regulation system is full wave rectified and has a PWM output for good motor starting capability and stability when powering non-linear loads. Major system features include:

Digital Output Voltage Regulation - PowerCommand will regulate output voltage to within 0.5% for any loads between no load and full load. Voltage drift will not exceed plus or minus 0.5% for a 60F (33C) change in temperature in an 8 hour period. On engine starting, or sudden load acceptance, voltage is controlled to a

maximum of 5% overshoot over nominal level. Control is configurable for operation of self-excited or separately-excited alternators.

Torque-Matched Volts/Hz Overload Control - The rate of decay (i.e., the slope of the volts/hertz curve) is adjustable in the control.

Fault Current Regulation - PowerCommand will

regulate the output current on any phase to a maximum of 3 times rated current under fault conditions for both single phase and three phase faults. The regulation system will drive a permanent magnet generator(PMG) to provide 3 times rated current on all phases for motor starting and short circuit coordination purposes.