Engine Protection

§ Overspeed Shutdown - Default setting is 115%

of nominal. § Low Lube Oil Pressure Shutdown - Level is

preset to match the capabilities of each engine. Control includes time delays to prevent nuisance shutdown signals. § Low Lube Oil Pressure Warning - Level is preset

to match the capabilities of each engine. Control includes time delays to prevent nuisance shutdown signals. § High Coolant Temperature Shutdown- Level is

preset to match the capabilities of each engine. Control includes time delays to prevent nuisance shutdown signals. § High Coolant Temperature Warning - Level is

preset to match the capabilities of each engine. Control includes time delays to prevent nuisance shutdown signals. § Low Coolant Level Warning/Shutdown § Low Coolant Temperature Warning. Indicates

that engine temperature may not be high enough for a 10-second start or proper load pickup. § Low and High Battery Voltage Warning -

Indicates battery charging system failure by continuously monitoring battery voltage. § Weak battery warning - The control system will

test the battery bank each time the generator set is signaled to start, and indicate a warning if the generator set battery indicates impending failure. § Fail to Start (Overcrank) Shutdown

§ Fail to Crank Shutdown - Control has signaled

starter to crank engine but engine does not rotate. § Redundant Starter Disconnect

§ Cranking Lockout. The control will not allow the

starter to attempt to engage or to crank the engine when the engine is rotating. § Sensor Failure Indication. All analog sensors

are provided with sensor failure logic to indicate if the sensor or interconnecting wiring has failed. Separate indication is provided for fail high or low.

AmpSentryTM

AmpSentry is a comprehensive monitoring and control system integral to the PowerCommand control that guards the electrical integrity of the alternator and power system by providing protection against a wide array of fault conditions in the generator set or in the load. It also provides single and 3-phase fault current regulation, so that downstream protective devices have the maximum current available to quickly clear fault conditions, without subjecting the alternator to potentially catastrophic failure conditions. See

document R1053 for a full size time overcurrent curve.

CUMMINS---PCC3100

10

Seconds

1

0.03

1

Functions included:

10 Amps ( x rated)

§ Over Current Warning - Output current on any

phase at more than 110% of rating for more than 60 seconds, or more that 400% for more than 1 second. § Over Current Shutdown (51) - Output current on

any phase is more than 110%, less than 175% of rating, and approaching thermal damage point of alternator. Control includes algorithms to protect alternator from repeated over current conditions over a short period of time. § Short Circuit Shutdown -Output current on any

phase is more than 110%, more than 175% of rating, and approaching thermal damage point of alternator. Control includes algorithms to protect alternator from repeated over current conditions over a short period of time.

上一页第5页