Alphanumeric Display Panel

The PowerCommand control is provided with an

alphanumeric display capable of displaying 2 lines of data with approximately 20 characters per line. The display is accompanied by a set of five tactile feel membrane switches that are used by the operator to navigate through control menus, and to make control adjustments. (There are no rotary potentiometers in the control. All adjustments are made via the display panel or InPower.) Display is configurable for multiple languages. It is configurable for units of measurement. All data on the control can be viewed by scrolling through screens with the navigation keys.

The control displays all active fault conditions with the latest displayed first. Active and inactive faults are displayed.

The display panel includes a screen-saver timer that will turn off the display after 10 minutes of inactivity. Touching any key will turn the screen back on. Generator Set Hardware Data - Generator set rating in kVA, Generator set model number. The control stores the software version present in the control. Data Logs - Number of start attempts and duration of generator set running time. Generator set kWh produced.

Fault History - Provides a record of the most recent fault conditions with time stamp. Up to 20 events are stored in the control non-volatile memory.

Load Profile Data – Control logs data indicating the operating hours at percent of rated kW load, in 10% increments. InPower is used to read this.

Generator Set Output Voltage - all phases, line to line and line to neutral, accuracy 1%. Data for all phases is displayed simultaneously to allow viewing of voltage balance.

Generator Set Output Current - all phases, accuracy 1%. Data for all phases is displayed simultaneously to allow viewing of load balance. Generator Set Output Frequency

Generator Set Power Output - PowerCommand displays generator set kW (total power), and power factor with leading/lagging indication. Accuracy 5%. Generator Set kWh Power Output - Displays total kilowatt-hours produced by the generator set. Engine Starting Battery Voltage Engine Lube Oil Pressure Engine Coolant Temperature Engine Lube Oil Temperature Engine Exhaust Temperature (Option)

Service Adjustments – The operator panel includes provisions for adjustment and set up of all control

functions in the generator set. The operator panel includes an access code that is used to protect the control from unauthorized service level adjustments.

Internal Control Functions Engine Control

Remote Start Mode - PowerCommand accepts a

ground signal from remote devices or a network signal to automatically start the generator set and immediately accelerate to rated speed and voltage.

PowerCommand includes a Smart Starting system, that is designed to quickly start the engine, minimize black smoke, and minimize voltage and frequency overshoot and oscillations on starting. The control system does this by careful control of the engine fuel system and alternator excitation system.

The control can incorporate a time delay start and a warm-up period at idle speed. See Engine Governing for details.

Sleep Mode – PowerCommand can be configured to include a sleep mode. When enabled, and when the mode select switch is in the OFF position, the control will revert to a low power consumption mode until a control switch on the operator panel is operated or a remote start signal is received.

Fault Simulation Mode - PowerCommand, in conjunction with InPower software, will accept

commands to allow a technician to verify the proper operation of all protective functions of the control, by simulating failure modes or by forcing the control to operate outside of its normal operating ranges. Engine Starting – The control system automatically controls the engine starter, and provides proper engine fueling and alternator control to provide fast and efficient starting.

Cycle Cranking - Configurable for number of starting cycles (1 to 7) and duration of crank and rest periods. Control includes starter protection algorithms to prevent the operator from specifying a starting sequence that might be damaging.

Time Delay Start And Stop (cooldown) -

Configurable for time delay of 0-300 seconds prior to starting after receiving a remote start signal, and for time delay of 0-600 seconds prior to ramp to idle or shut down after signal to stop in normal operation modes. Default for both time delay periods is 0 seconds.