Operator Panel
The operator panel provides the user with a complete package of easy to view and use information.
Connections to the operator panel are locking plug interfaces, for reliable, vibration-resistant
interconnection to the generator set wiring harness. Control Switches and Functions
§ RUN/OFF/AUTO Mode Control Switch - The
NOT IN AUTO lamp will flash when the control is in the RUN or OFF mode. In the AUTO mode, the generator set can be started with a start signal from a remote device, such as an automatic
transfer switch. In the RUN position the generator set will start and accelerate to rated speed and voltage. In the RUN mode, the control can be configured to operate at idle speed with the excitation switched off. § PANEL LAMP Control Switch – Depressing the
panel lamp switch will cause the panel illumination to operate for approximately 8 minutes. § EMERGENCY STOP Control Switch – Pressing
the emergency stop switch will cause the generator set to immediately shut down. The generator set is prevented from running or cranking with the switch pressed in. § RESET Switch. Clears the digital display and
status panel and allows the generator set to be started after a fault has been corrected. § SELF TEST Switch. Prompts the control to
perform a self-test of the system, and displays all fault messages. § PHASE SELECT Switch. Controls the phase that
is displayed on the analog AC Instrumentation. § Operator Adjustments. The control includes
provisions for many set up and adjustment
functions via raise/lower switches on the operator panel. Functions that can be adjusted by the operator include:
Time delay start (0-300 seconds) Time delay stop (0-600 seconds) Alternator voltage (plus or minus 5%) Alternator frequency (plus or minus 5%)
Indicating Lamps
The operator panel includes a series of LED indicating lamps to allow the operator to view the general status of the generator set. Functions displayed include: · · ·
Red (flashing) lamp to indicate Not-in-Auto mode; and a red lamp to indicate common shutdown. Amber lamp for common warning.
Phase and Scale Indication. Indicates the phase that is displayed on the analog AC instruments.
Analog AC Metering Panel
The PowerCommand control is equipped with an
analog AC metering panel that displays 3-phase line to line AC volts and current, kW, and frequency.
Analog metering on the control panel provides clear indication of generator set stability, including the
magnitude of displacement and rate of change during lead transients, which cannot be viewed a clearly with digital metering equipment. These meters are also ideal for “walk-by” status checks by the operator. All meters are 2.5-inch (63.5mm), 90-degree scale. Meter faces UV protected against discoloration from exposure to sunlight. The kilowatt meter and ammeter are scaled in percent of AC output for easy recognition of
generator set status and load level (0-90% of rating: green; 90-100% of rating: amber; >100% of rating: red).
· % Kilowatt Meter: Indicates 3-phase AC power
output as a percent of rated load. Provides a true indication of total kW load on the generator set, regardless of the load power factor. Scale is 0-125%. Accuracy is ±5%.
· Frequency Meter: Indicates generator set output
frequency in hertz. Calculated frequency is based on engine speed and alternator voltage zero-crossing and is not affected by voltage waveform distortion caused by non-linear loads. Scale is 45-65 Hz. Accuracy is ±0.5 Hz.
· AC Voltmeter: Dual scale AC voltmeter indicates
alternator output voltage. Accuracy: ±2%. Scales: 0-300VAC, 0-600 VAC; 0-400 VAC, 0-750 VAC; 0-5260 VAC; or 0-15,000 VAC.
· % AC Ammeter: Indicates current output in
percent of maximum rated standby current. Accuracy: ±2%. Scale: 0-125%..
2004 年 8 月修订 第 1-1 康明斯东亚培训中心 康明斯 PCC3100 控制器培训讲义万世祥 编辑 2004 年 8 月修订 第 1-2 康明斯东亚培训中心 康明斯 PCC3100 ...
电路板位置 2004 年 8 月修订 第 1- 2页 康明斯东亚培训中心 康明斯 PCC3100 控制器培训讲义万世祥 编辑 方框图 2004 年 8 月修订 第 1- 3页 康明斯东亚...
康明斯2012柴油发电机并机控制器 Digital PC3100 正式...Cummins Power Generation, and are covered by a ...康明斯柴油发电机组PCC3... 13页 1下载券 东风康明斯...
康明斯东亚培训中心 康明斯 PCC3100 控制器培训讲义万世祥 编辑 第 2 章 PCC3100 操作介绍本节介绍发电机组的一般操作,发电机组的具体操作步骤及注意事项请严格按...
3100 3100 3100 3300 3450 3350 3550 3750 4350 4650 4650 4650 4850 1200 1212 1212 1212 1400 1466 1488 2020 1790 1870 1870 1870 1870 2070 960 972 972...
3100*1050*1750 3000KG 1、柴油机主要参数 品牌: 产地: 柴油机型号: 最大功率: 类型: 冷却方式: 排列型式: 气缸数: 缸径*行程: 排量: 机油容量: 转速: ...
(从空载到 100%负载) 5.14 机组外形尺寸:长×宽×高约 3100×940×1690mm(具体实际尺寸详见正式蓝图) 六、机组结构组成 6.1 柴油机 6.1.1 柴油机厂商与...
3100×1060×1900 3050×970×1600 3100×1060×1900 3100×1060×1900 3100×1060×1900 3300×1090×1850 3400×1300×2000 3300×1090×1850 3400×1300×2000...
3100×1050×1800 330GF1 360GF 330GF 400GF 450GF 420GF 505GF 520GF ...康明斯柴油发电机组PCC3... 21页 1下载券 300KW康明斯柴油发电机组... 3页 ...
·h 外形尺寸:3100×1250×1650(L×W×H mm) 发动机冷却方式:满足环境温度 40℃散热器,皮带驱动冷却风扇 发电机技术参数: 材质: 纯铜 电压控制方式:AVR 额定...