Two phase convective cooling for ultra-high power dissipation in microprocessors

超高压电

exiting enthalpy is the same, as required by Eq. (11). The additional pressure drop due to friction predicted for this system is significant, and induces a greater accelerational pressure drop as well, due to greater density decrease accompanying greater pressure drop. In the depicted example, We consider the simple case of uniformly applied heat flux, so

that Eq. (6) can be integrated analytically, yielding

q

(11) h z h(0) z

The accelerational pressure drop term in Equation (7) can be expanded using

1x2 1 x 2

(12) v 1 l

which requires a model for determination of the void fraction, . We have used both the homogeneous mixture model (HMM) and the annular kinetic energy model of Zivi, both of which can be compactly written as [10]

1 1 n x 1v (13) l where Results n=1 (11)-(13) in EES using the Euler method.

are for obtained the HMM, through and solution n=2/3

for of the Eqs. model (7), (8), of Zivi. and Results of Reduced Order Analysis coolants We have model produces solutions that agree with the thermodynamic represented investigated in Figs. the 3-6. performance First, we of verified several that of the the analysis frictional when the friction factor is set Integration of Eq. (8) using the Euler method with 100 equal pressure drop) to validate proper to implementation. zero (removing length spatial steps resulted in a predicted pressure drop within 2% (3).

of the results obtained using the analytical solution, Eq. friction, friction was then included, and, as expected, we find

Having validated the model implementation without that which correlates to coolants with higher saturation pressures. the impact of friction is greater for larger mass fluxes, In Fig. 7 we present the results of refrigerant operate as a coolant at above ambient temperatures. With and that would require very a simulation for R134a, a high system pressures to without friction, and regardless of void fraction model, the Fig. 7 Comparison using of results with and without friction, determination for R134a in a 154 the HMM and model of Zivi for void fraction and long, with m microgap, 1 cm kW/cm2diagram with the saturation dome in black. . Results G=7,000 kg/(m2are plotted s), Ton in = 358.15 K, anda pressure-enthalpy q''=1 using included increased by slightly greater than a factor of 5, from the Zivi model, the total pressure drop with friction 239 COP kPa to 1.26 MPa. The included using Eqs. (4) and (5) predicted COP is is similarly large: with corresponding entrance and exit effect pressure on system friction 46 without drop drops at these microgap geometries, power dissipation levels, included, and 7.5 with it (Fig. 6). Clearly, pressure degrees friction.

of vaporization, and mass fluxes, are dominated by

on the predicted pressure drops. This is not surprising, as, in The choice of void fraction model has a very small effect the qualities of 0 and 1, respectively, the choice limiting case of no friction and inlet and outlet vapor model has no impact on predicted drop, variation along although void the it does slightly total alter accelerational pressure of void fraction

the path of pressure

convenience in this type of analysis. fraction models cooling could passage. This results perhaps be chosen implies based that on although it has very little effect in the example shown in Fig 7. Friction can also affect vapor quality at the microgap exit, The the shape of the saturation dome in the pressure range of the effect of increased pressure drop on quality depends on microgap, with quality increasing when dhv

0 but expected to decrease whenever dhv 0. Overall, friction reduces the

potential improvements in heat transfer coefficient indicated in Figs. 3 & 4, both by shifting the overall “trend” line down and by moving the maxima for each coolant to the left on the line. This effect is partially mitigated, however, by the reduction in temperature that accompanies lower pressure for the saturated fluids, as temperatures lower flux. positive The lower for fluid the same temperatures imply heat transfer coefficient lower wall/junction

and heat exponentially reducing the leakage current, which is especially implication wall/junction on the temperature transistor has performance a significant by relevant when a cooling system is imbedded (i.e., located in a close conventionally implemented as part of the package.

proximity) into an electronic device rather than using Conducting more the idealized parametric thermodynamic studies such as that performed order model tedious thermodynamic (this is and difficult one of the with motivations the model more realistic is significantly reduced Nevertheless, in order to obtain some indication of the degree model to identify possible behind using trends). the to which friction might impact the previously identified trend, we condition found the optimum (largest k/H R245fa coolant/ with for R134a with T = 358.15 at and full 308.15, vaporization)

inand for

data points across a representative range of pressures, and the inlet temperature Tin = 328.15. conditions These were three chosen combinations to provide of results dramatically are included reduces the in expected Fig. 4. The heat inclusion transfer

Two phase convective cooling for ultra-high power dissipation in microprocessors

performance of friction