文档下载 文档下载导航
设为首页 | 加入收藏
搜索 请输入内容:  
 导航当前位置: 文档下载 > 所有分类 > 工程科技 > 电子/电路 > Experience with Synchronous Generator
侵权投诉

Experience with Synchronous Generator

Experience with Synchronous Generator Parameter Identification using a Kalman Filter

Kang Lin, Member, IEEE, Elias Kyriakides, Senior Member, IEEE, Gerald T. Heydt, Life-Fellow,

IEEE, Naim Logi , Senior Member, IEEE, and Bharat Singh, Member, IEEE

rameters. For example, [11] estimates machine parameters from Standstill Frequency Response (SSFR) test data, and [12], [13] perform parameter identification using the recursive maximum likelihood technique. Least squares techniques are Abstract — The subject of the identification of the equivalent

circuit parameters of large synchronous generators is revisited. The equivalent circuit of Park is used. On-line measurements are used in a Kalman filter to estimate the machine parameters. The formulation is linear and the extended Kalman filter is not needed. The approach is similar to that of Harley (1992), but flux linkages are not used in the present formulation in the ma-chine model vector. An example is shown for an actual machine in operation in the Southwest United States. A transition to real time data using synthetic synchronized measurements (e.g., from a phasor measurement unit) is proposed and demonstrated.

Index Terms — Kalman filter, machine parameters, parame-ter identification, synchronous generator, phasor measurement unit, PMU, synchrophasor.

I. THE PARAMETER IDENTIFICATION OF LARGE

S

SYNCHRONOUS GENERATORS

YNCHRONOUS generator parameter identification con-tinues to attract considerable attention [1]-[4]. Knowledge

of the operational parameters of generators is necessary

for performing stability studies and post mortem analyses of

failures. In general, synchronous generator parameters are not constant throughout the useful life of the machine. Factors such as aging and machine repairs (e.g., rewinding) cause permanent changes to machine parameters; magnetic satura-tion causes temporary changes to the machine magnetizing inductances according to the operating point of the machine. Synchronous machine parameters may be obtained by off-line tests as described in the IEEE Standards [5], [6]. However, these tests cannot adequately address operating changes of the machine, while at the same time they are expensive and neces-sitate decommitment of the machine for at least a week at in-tervals of about two years. For these reasons, on-line parame-ter estimation is necessary to ensure that the parameters used in different power system studies are accurate, and to enhance the confidence in the interpretation of the results of such stu-dies. Several parameter estimation methods are based on the

Park’s equivalent machine model [7], [8]. Some examples of

these methods include [1], [2], [9], [10]. A wide range of es-timation techniques have been used to determine machine pa- The authors acknowledge the support of the Power Systems Engineering Research Center under grant NSF EEC-0001880, the Salt River Project, and the Cyprus Research Promotion Foundation.

K. Lin and G. T. Heydt are with the Department of Electrical, Computer and Energy Engineering at Arizona State University, Tempe, AZ, USA (e-mail: {kang.lin}, {heydt}@asu.edu). E. Kyriakides and B. Singh are with the KIOS Research Center for Intelligent Systems and Networks and the Depart-ment of Electrical and Computer Engineering at the University of Cyprus, Nicosia, Cyprus (e-mail: {elias}, {bharat}@ucy.ac.cy). N. Logi is with the Salt River Project, Phoenix AZ (e-mail: naim.logic@srpnet.com).

978-1-4244-6551-4/10/$26.00 ©2010 IEEE

used for examples in [1] and [2]. In [14] generator and exciter parameters are estimated after a hydro unit is reworked to up-grade the machine.

In the 1990s, Harley and others suggested the use of a Kal-man filter to identify synchronous machine parameters [15], [16]. A Kalman filter is an estimator [17]. This estimator can be used to track a dynamic process. The Kalman filter ap-proach requires an assumption of the model of the process being tracked – in the case studied in this paper, Park’s model.

In Harley’s work, the Kalman approach to synchronous para-meter identification was demonstrated successfully. In the present paper, this work is extended in the sense that magnetic flux linkages are not used in the model, and the resultant for-mulation is demonstrated on an actual generator in service.

II. PARK’S MODEL AND SYNCHRONOUS MACHINE MODELING

Robert H. Park developed a model for large synchronous generators in the 1920s [7], [8] and this model has served the power industry for many years. While this is not the only model in use for large generators (e.g., [18]), power engineers usually specify synchronous generators in terms of their Park model parameters and various parameters derived from them. The basic mathematical model is derived from,

v= ri λ

&, (1) where r is the winding resistance, i is the current and λ is the flux linkage. It should be noted that in this notation it is as-sumed that the direction of positive stator currents is out of the terminals, since the synchronous machine under consideration is a generator. Park’s model is effectively enabled through a transforma-tion of abc quantities to an equivalent 0dq set of quantities, that refers all quantities to a rotor frame of reference. Park’s transformation is given by [7], [8],

111 2 P=

22 cos θcos(θ 2)cos(θ sinθsin(θ

2+2π) , (2) )sin(θ+2)

where the angle θ is given by,

θ=ωRt+δ+π2. (3)

In (3) ωR is the rated (synchronous) angular frequency in rad/s and δ is the synchronous torque angle in electrical radians.