Design of robust control and monitoring system for microgrid stabilization
Design of Robust Control and Monitoring System for Microgrid Stabilization
Sitthidet Vachirasricirikul*, Issarachai Ngamroo**, Somyot Kaitwanidvilai** and Theerawut Chaiyatham*
*Department of Electrical Engineering, Faculty of Engineering, King Mongkut’s Institute of Technology
Ladkrabang, Bangkok 10520, Thailand (e-mail: sitthidetv@hotmail.com)
**Center of Excellence for Innovative Energy Systems, King Mongkut's Institute of Technology
Ladkrabang, Bangkok 10520, Thailand
Abstract-This paper proposes a design of the robust control
and monitoring system (RCMS) for stabilization of microgrid (MG) system. The power sources in MG consists of wind power (WP), photovoltaic (PV), micro-turbine (MT) and fuel cell (FC). Due to intermittent powers from WP, PV and load fluctuations, the MG stabilization of RCMS is performed by controlling the power outputs of MT and electrolyzer system (ES) in both islanding and interconnected utility grid operations. The structure of MT and ES controllers is the proportional integral (PI). By taking system uncertainties into account, control parameters of MT and ES are simultaneously optimized based on the particle swarm optimization (PSO) based fixed-structure H∞ loop shaping control. Simulation results show the robustness and effectiveness of the proposed RCMS against the variation of system parameters and operating conditions.
Key-words: Microgrid, robust control, H∞ loop shaping
control, particle swarm optimization
I. INTRODUCTION
Presently, there are many remote areas around the world which are not still connected with the main utility grid due to the environment and investment. Therefore, the microgrid (MG) system is an essential choice to solve this problem. The MG is a group of the distributed generation (DG) units, distributed storage (DR) units and loads. Furthermore, the MG can be operated independently in a stand-alone mode and also interconnected to the utility grid [1]. In this paper, wind power (WP), photovoltaic (PV), micro-turbine (MT), electrolyzer system (ES), fuel cell (FC), hydrogen tank (H2T), control and monitoring system (CMS), load, transformer (TR) and utility grid (UG) are combined in the system of MG. The ES is utilized to consume the output power and also build hydrogen for FC. Normally, the WP and PV are highly intermittent. Thus, the real power
unbalance of generations and load demands can cause the
frequency fluctuation problem. Also, when the MG is
connected to in the UG, not only the frequency deviation but
also the tie line power fluctuations are an inevitable problem. To tackle these problems, the CMS is utilized to control the real power mismatch of generation and load. In [2-3], the proposed CMS is applied to suppress the fluctuations of frequency and tie line power in MG via controllable power outputs of MT and ES. However, the controller parameters of MT and ES are separately tuned for islanding and interconnected utility grid operations. As a result, the CMS can not guarantee the well coordinated control effect. Besides, these works do not take system uncertainties such as
978-1-4244-3388-9/09/$25.00 ©2009 IEEE
the variation of system parameters etc., into consideration. Accordingly, the robustness of CMS against system uncertainties can not be guaranteed. The CMS with coordinated controllers with high robustness is expected. To overcome this problem, this paper focuses on the design of robust control and monitoring system (RCMS) for MG stabilization. The intermittent power outputs due to WP and PV as well as load fluctuations cause frequency fluctuation in the MG. To stabilize MG, the RCMS is designed to control the power outputs of MT and ES. For practical realization, the structure of MT and ES controllers is a proportional integral (PI). To improve the coordinated control effect and robustness against system uncertainties of MT and ES, the particle swarm optimization (PSO) [4] based
fixed-structure H∞ loop shaping control is applied. Unstructured system uncertainties are modeling by normalize
coprime factor [5]. Based on an enhancement of robust
stability margin in H∞ control concept, PI controller
parameters of MT and ES in islanding and interconnected
utility grid modes are concurrently tuned. Simulation results
confirm the superior stabilizing effects of RCMS via MT and ES in both islanding and interconnected grid modes in comparison to the CMS in [2-3]. II. SYSTEM

MODELING Figure 1. A MG system.
A MG system in Fig.1 consists of WP, PV, MT, ES, H2T, FC, RCMS, load, TR and UG. The ES is applied to absorb the output power and construct hydrogen as operated fuel for FC. The MT is used to supply power to system when WP and PV can not adequately provide. The WP, PV and load changes cause a problem of frequency fluctuation in an islanding mode as well as, frequency and tie-line power fluctuation in an interconnected grid mode. To stabilize MG, the real time control of RCMS via the power outputs of MT and ES is performed.
The block diagram of MG system is shown in Fig.2. The
System for Frequency Control in Microgrid System K...stabilization from the battery system, PRR is ...V. THE CONTROLLER DESIGN OF THE BATTERY ENERGY ...
16 Design of Robust Power System Stabilizer in ...effective machines for stabilization have been ...Despite the significant potential of control ...
Robust stabilization and disturbance attenuation for a class of underactuated mechanical system_专业资料。JCetSuhUi.21)928—45.n.ot nv(021:4829 DoI010/l...
A robust control approach to stabilization of ...The stochastic system approach may not be ...(2004). State feedback controller design of ...
The Status of DC microgrid protection_电力/水利... allowing for a more robust de-centralized ...Protective System Design It has long been ...
for Isolated Power System Stabilization Eitaro Omine...enables intuitive controller design in frequency ...control, frequency control, H∞ control, microgrid...
Such a design problem is referred to as semi-global practical stabilization ...International Journal of Robust and Nonlinear Control 1995; 5:375–380. 2....
Design of system protection philosophy with a ... monitoring and control of all microgrid assets ...stabilization, as well as other ancillary system ...
Such a design problem is referred to as semi-global practical stabilization ...International Journal of Robust and Nonlinear Control 1995; 5:375–380. 2....