Design of robust control and monitoring system for microgrid stabilization
detailed blocks of each power source are given in [2,3]. The control objective of RCMS is to minimize the real power mismatch between generation and load powers (ΔP). The linearized block of RCMS is exhibited in Fig.3. Note that the real-time control of FC [2-3] is not considered in this paper and the output power of FC is set as a constant value of 5 output signal Δu = [ΔPMTis ΔPESis ΔPMTug ΔPESug]T. ΔPMTis and ΔPESis are changes in the side of islanding operation of MT output and ES load, respectively. ΔPMTug and ΔPESug are changes in the side of interconnected utility grid operation of MT output and ES load, respectively. KPMTis(s), KPESis(s) and KPMTug(s), KPESug(s) are the designed MT and ES controllers kW.

Figure 2. A diagram of MG system.

RCMS.
In Fig.3, the linearized state can be expressed as
ΔX
=AΔX+BΔu (1)ΔY=CΔX+DΔu ΔP(2)MTis=KPMTis(s))ΔP (3)ΔPESis=KPESis(sΔP (4)ΔPMTug=KPMTug(s)ΔPtie
(5)ΔPESug=KPESug(s)ΔPtie
(6)KPMTis(s)=KP_MTis+KI_MTiss (7)KPESis(s)=KP_ESis+KI_ESiss
(8)KPMTug(s)=KP_MTug+KI_MTugs (9)KPESug(s)=KP_ESug+KI_ESugs
(10)
where the state vector ΔX = [ΔPES ΔPtie Δf]T
. ΔPES, ΔPtie and Δf are changes of ES load, tie line power and frequency, respectively. The output vector ΔY = [ΔP ΔPtie]T
, the control in the islanding and interconnected utility grid modes, respectively. Note that all four controllers are operated in the interconnected utility grid mode while the KPMTis(s) and KPESis(s) are performed in the islanding mode. The system (1) is a multi-input multi-output (MIMO) system and referred to the nominal plant G.
III. THE PROPOSED DESIGN TECHNIQUE
The proposed design technique is represented as follows: A. Formulate the shaped plant Gs
As demonstrated in Fig.4, the shaped plant Gs =W2GW1 is enclosed by a solid line. The proposed robust controller K=W1K∞W2 is enclosed by a dotted line. K∞ is the H∞

controller.
Figure 4. Shaped plant G and robust Controller
K.
B. Selection of the weighting functions
The shaped plant (Gs) in Fig.4 can be established by choosing the weighting functions as
WMTis0
0
W0WESis0
0 1=
,W=I
00WMTug0 2
0
00W
ESug WsMTis=KW1+a1,s+bWsESis=KW2
+a2,
1s+b2Ws+aMTug=KW33,s+a4s+bWESug=KW4
(11)
3s+b4
where WMTis, WESis and WMTug, WESug are the weighting functions of MT output and ES load in the sides of islanding and interconnected utility grid modes, respectively. KW1, a1, b1, KW2, a2, b2, KW3, a3, b3, KW4, a4 and b4 are the positive values. Because the peak of resonance is in the low frequency range. So, W1 is set as a high-pass filter (a1 < b1, a2 < b2, a3 < b3, a4 < b4).

C. Evaluate the robust stability margin of the system
Figure 5. H∞robust stabilization problem.
In this work, variation of system parameters, generating
and loading conditions etc., are defined as unstructured
system uncertainties. Because these uncertainties can not
be clearly represented by mathematic equations, the coprime
Figure 3. Linearized block diagram of
System for Frequency Control in Microgrid System K...stabilization from the battery system, PRR is ...V. THE CONTROLLER DESIGN OF THE BATTERY ENERGY ...
16 Design of Robust Power System Stabilizer in ...effective machines for stabilization have been ...Despite the significant potential of control ...
Robust stabilization and disturbance attenuation for a class of underactuated mechanical system_专业资料。JCetSuhUi.21)928—45.n.ot nv(021:4829 DoI010/l...
A robust control approach to stabilization of ...The stochastic system approach may not be ...(2004). State feedback controller design of ...
The Status of DC microgrid protection_电力/水利... allowing for a more robust de-centralized ...Protective System Design It has long been ...
for Isolated Power System Stabilization Eitaro Omine...enables intuitive controller design in frequency ...control, frequency control, H∞ control, microgrid...