 导航当前位置: 文档下载 > 所有分类 > 工程科技 > 能源/化工 > Design of robust control and monitoring system for microgrid stabilization
侵权投诉

Design of robust control and monitoring system for microgrid stabilization

Design of robust control and monitoring system for microgrid stabilization

detailed blocks of each power source are given in [2,3]. The control objective of RCMS is to minimize the real power mismatch between generation and load powers (ΔP). The linearized block of RCMS is exhibited in Fig.3. Note that the real-time control of FC [2-3] is not considered in this paper and the output power of FC is set as a constant value of 5 output signal Δu = [ΔPMTis ΔPESis ΔPMTug ΔPESug]T. ΔPMTis and ΔPESis are changes in the side of islanding operation of MT output and ES load, respectively. ΔPMTug and ΔPESug are changes in the side of interconnected utility grid operation of MT output and ES load, respectively. KPMTis(s), KPESis(s) and KPMTug(s), KPESug(s) are the designed MT and ES controllers kW.

Design of robust control and monitoring system for microgrid stabilization

Figure 2. A diagram of MG system.

Design of robust control and monitoring system for microgrid stabilization

RCMS.

In Fig.3, the linearized state can be expressed as

ΔX

=AΔX+BΔu (1)ΔY=CΔX+DΔu ΔP(2)MTis=KPMTis(s))ΔP (3)ΔPESis=KPESis(sΔP (4)ΔPMTug=KPMTug(s)ΔPtie

(5)ΔPESug=KPESug(s)ΔPtie

(6)KPMTis(s)=KP_MTis+KI_MTiss (7)KPESis(s)=KP_ESis+KI_ESiss

(8)KPMTug(s)=KP_MTug+KI_MTugs (9)KPESug(s)=KP_ESug+KI_ESugs

(10)

where the state vector ΔX = [ΔPES ΔPtie Δf]T

. ΔPES, ΔPtie and Δf are changes of ES load, tie line power and frequency, respectively. The output vector ΔY = [ΔP ΔPtie]T

, the control in the islanding and interconnected utility grid modes, respectively. Note that all four controllers are operated in the interconnected utility grid mode while the KPMTis(s) and KPESis(s) are performed in the islanding mode. The system (1) is a multi-input multi-output (MIMO) system and referred to the nominal plant G.

III. THE PROPOSED DESIGN TECHNIQUE

The proposed design technique is represented as follows: A. Formulate the shaped plant Gs

As demonstrated in Fig.4, the shaped plant Gs =W2GW1 is enclosed by a solid line. The proposed robust controller K=W1K∞W2 is enclosed by a dotted line. K∞ is the H∞

Design of robust control and monitoring system for microgrid stabilization

controller.

Figure 4. Shaped plant G and robust Controller

K.

B. Selection of the weighting functions

The shaped plant (Gs) in Fig.4 can be established by choosing the weighting functions as

WMTis0

0

W0WESis0

0 1=

,W=I

00WMTug0 2

0

00W

ESug WsMTis=KW1+a1,s+bWsESis=KW2

+a2,

1s+b2Ws+aMTug=KW33,s+a4s+bWESug=KW4

(11)

3s+b4

where WMTis, WESis and WMTug, WESug are the weighting functions of MT output and ES load in the sides of islanding and interconnected utility grid modes, respectively. KW1, a1, b1, KW2, a2, b2, KW3, a3, b3, KW4, a4 and b4 are the positive values. Because the peak of resonance is in the low frequency range. So, W1 is set as a high-pass filter (a1 < b1, a2 < b2, a3 < b3, a4 < b4).

Design of robust control and monitoring system for microgrid stabilization

C. Evaluate the robust stability margin of the system

Figure 5. H∞robust stabilization problem.

In this work, variation of system parameters, generating

and loading conditions etc., are defined as unstructured

system uncertainties. Because these uncertainties can not

be clearly represented by mathematic equations, the coprime

Figure 3. Linearized block diagram of