protection issue of the microgrid concept

微电网保护相关论文

x Re-synchronization to utility: enable automatically or manually, match frequency and voltage automatically or manually?

Implicit in this list is the acceptance of many concurrent factors. Microgrid means very small power capacity relative to the utility, e.g., less than 10 MVA. Any system that is designated as a microgrid will have sufficient generation sources to carry a significantportion of the microgrid’s load. As such, under improper separation from the utility, i.e., not at the PCC, it will have the possibility of carrying part of the utility. IEEE standards activity will soon be setting minimum interconnection protection criteria, which any microgrid may have to meet while operating interconnected. Economics is important.Finally, the reality that even excellent protection packages cannot compensate for all of the special needs to operate a microgrid must be recognized.

Rapid Separation from a Faulted Feeder

One of the goals of forming a microgrid is to maintain uninterrupted power to critical loads. As indicated above, if the loads of the microgrid are so sensitive to voltage dips that they require the system to meet SEMI F47 specifications, then existing protective equipment cannot act fast enough to separate from the fault under all conditions. Secure relay time to detect an under (or over) voltage can be up to two cycles. Most mediumvoltage breaker times, after receiving a trip signal, require from three to five cycles to interrupt the circuit. Therefore, unless the microgrid interface device at the point of common coupling is a solid state circuit breaker, other system design considerations will have to be employed to prevent the voltage from going below 50% for three cycles or longer.

SEMI F47Sag Immunity

100

90

80

70

60

50

40

30

20

10

0.010.11

Sag Duration (sec

protection issue of the microgrid concept

protection issue of the microgrid concept

)10100SagRide-ThroughRegion

Figure 2, SEMI F47 Voltage verses Time Limits