Making the decision of when to separate from the utility first requires a realistic expectation of what benefit the microgrid will gain from rapid separation. While

equipment standards such as SEMI F47 suggest that many manufacturers would benefit from separation times of less than 50 milliseconds after an abnormal condition is started on the utility, such times are not possible with presently available protective devices (as noted in footnote 1, below). If very high speed separation is required and nuisance trips are to be avoided (see the Nuisance Separation section below for a discussion of whether nuisance separations should be tolerated in a trade for improved reliability), then transfer trip systems must be installed between the utility substation and the breaker at point ofcommon coupling (PCC) with the microgrid. (Note that the PCC is the point where the Main Microgrid Separation Device is shown on figure 1.) Separating for non-fault

conditions will also benefit from having high-speed communication channels between the utility and the microgrid.

When the microgrid has separated from the utility, a host of new issues must be accommodated. A means to assure appropriate grounding must be provided. The equipment used for detection of faults internal to the microgrid must work with, or around, the protection that exists for fault detection while connected to the utility. A means of detecting faults that is not dependent on a large ratio between fault current and maximum load current must be provided. Any existing anti-islanding schemes will have to be examined, and perhaps modified, to prevent instability or loss of DR units with sensitive settings. Any load shedding schemes set up by the utility in the microgrid area will have to be closely coordinated.

The following sections explore these areas to determine what might be done with present protective devices to resolve these issues. Modern protection techniques are highly

evolved from nearly a century of experience. Thus caution should be used in any attemptsto revolutionize approaches to system protection.

Grid Separation

In a preliminary evaluation for this report, the following issues were listed for

consideration:

x Protection operation speed required to approach SEMI F47 specifications1

x Nuisance separations: how to minimize

x Is non-fault separation (for low voltage, open phase, voltage imbalance, etc.) desirable?

x Separation protection limitations imposed by microgrids that export power to the utility

Note that it is not possible, at least with electromechanical switching devices, to meet the SEMI F47 specification for all fault types and locations. The SEMI specification does not permit voltages below50%, even with durations as short as 0.05 sec. (3 cycles at 60 Hz.) If a utility feeder fault causes the

voltage to drop below 50%, there is nothing that can be done except to separate as quickly as possible (see Figure 2).

1