Warning
EN a CMC-DN01 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity,
electric shock and vibration. To prevent non-maintenance staff from operating CMC-DN01, or to prevent an accident from damaging CMC-DN01, the control cabinet in which CMC-DN01 is installed should be equipped with a safeguard. For example, the control cabinet in which CMC-DN01 is installed can be unlocked with a special tool or key.
EN a DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring
again before CMC-DN01 is powered up. After CMC-DN01 is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on CMC-DN01 is correctly grounded in order to prevent electromagnetic interference.
FR a CMC-DN01 est un module OUVERT. Il doit être installé que dans une enceinte protectrice (boitier, armoire, etc.)
saine, dépourvue de poussière, d’humidité, de vibrations et hors d’atteinte des chocs électriques. La protection doit éviter que les personnes non habilitées à la maintenance puissent accéder à l’appareil (par exemple, une clé ou un outil doivent être nécessaire pour ouvrir a protection).
FR a Ne pas appliquer la tension secteur sur les bornes d’entrées/Sorties, ou l’appareil CMC-DN01 pourra être
endommagé. Merci de vérifier encore une fois le câblage avant la mise sous tension du CMC-DN01. Lors de la déconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante. Vérifier que la terre est bien reliée au connecteur de terre afin d’éviter toute interférence électromagnétique.
X Introduction
Thank you for choosing Delta CMC-DN01 network communication card. CMC-DN01 is a DeviceNet network communication card for connecting Delta C2000 series, CH2000 series, CP2000 series, CT2000 series, and AFE2000 series AC motor drives to DeviceNet network.
Functions
1. Based on the high-speed communication interface of Delta HSSP protocol, able to conduct immediate
control to AC motor drive.
2. Supports Group 2 only connection and polling I/O data exchange.
3. For I/O mapping, supports Max. 32 words of input and 32 words of output. 4. Supports EDS file configuration in DeviceNet configuration software.
5. Supports all baud rates on DeviceNet bus: 125kbps, 250kbps, 500kbps and extendable serial transmission
speed mode.
6. Node address and serial transmission speed can be set up on AC motor drive. 7. Power supplied from AC motor drive.

[Figure 1]
1. NS indicator 2. MS indicator
3. POWER indicator 4. Positioning hole 5. DeviceNet connection port 6. Screw fixing hole 7. Fool-proof groove
8. AC motor drive connection port
Y Specifications
DeviceNet Connector
Interface
5-PIN open removable connector. Of 5.08mm PIN interval Transmission method CAN
Transmission cable Shielded twisted pair cable (with 2 power cables)
Transmission speed 125kbps, 250kbps, 500kbps and extendable serial transmission speed mode Network protocol
DeviceNet protocol
AC Motor Drive Connection Port
Interface
50 PIN communication terminal Transmission method SPI communication
Terminal function
1. Communicating with AC motor drive
2. Transmitting power supply from AC motor drive
Communication protocol Delta HSSP protocol
Electrical Specification
Power supply voltage 5VDC (supplied by AC motor drive) Insulation voltage 500VDC Communication wire power consumption 0.85W Power consumption
1W
Environment
ESD (IEC 61800-5-1,IEC 6100-4-2)
Noise immunity
EFT (IEC 61800-5-1,IEC 6100-4-4)
Surge Test (IEC 61800-5-1,IEC 6100-4-5)
Conducted Susceptibility Test (IEC 61800-5-1,IEC 6100-4-6)
Operation /storage Operation: -10ºC ~ 50ºC (temperature), 90% (humidity), pollution degree 2 Storage: -25ºC ~ 70ºC (temperature), 95% (humidity, non-condensing)
Shock / vibration International standards: IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 resistance
(TEST Ea)
Z Installation
Note: The contents below are about installing CMC-DN01 on C2000.

DeviceNet Connector
PIN
Signal
Color
Definition
DC24V Signal+ Earth

Signal- 0V

How to Install
① Use efficient tool to peel the communication cable for
Approx. 30mm
approx. 30mm. DO NOT damage the shielded cable while peeling.
② Peel off the metallic shielded net and foil and you will
see 2 power cables (in red and black), 2 signal cables (in blue and white) and 1 shielded cable.
③ Peel off the exterior metallic shielded net, foil and the
plastic cover of the power cable and signal cable in

proper length.

④ Insert the peeled communication cables into the holes
in the connector in correct order.
⑤ Tighten the screws on the connector by a slotted
screwdriver, and fix the communication cables in the



holes in the connector.
⑥ Install CMC-DN01 on C2000:
1. Switch off the power supply of C2000. 2. Open the cover on top of C2000.
3. Place the insulation spacer into the positioning pin, and aim the two holes on the PCB at the positioning pin. Press the pin to clip the holes with the PCB (see Figure 2).
4. Screw up at torque 6~8 kg-cm (5.21~6.94 in-lbs) after the PCB is clipped with the holes (see Figure 3).
[Figure 2] [Figure 3]
⑦ Connect to DeviceNet connector: Insert the connector to the connection port on CMC-DN01 (see
Figure4)
[Figure 4]
Communication Parameters for C2000 Connected to DeviceNet
When C2000 is connected to DeviceNet, please set up the communication parameters for it according to the table below. The DeviceNet master is only able to read/write the frequency word and control word of C2000
after the communication parameters are set.Parameter Function
Set value
Explanation
P00-20
command
8 the communication card.
P00-21
Setting up source of operation
command
5 The operation command is controlled by the communication card.
P09-30 Decoding method for communication 0 The old decoding method for the Delta AC motor drive
P09-70 Node address of communication card User defined Node address of C2000 in DeviceNet. P09-71
Serial transmission speed of communication card User defined
Serial transmission speed of C2000 in DeviceNet.
When P09-72 = 0, P09-71 will enter P09-72
Setting up mode for P09-71
User defined
standard mode.
When P09-72 = 1, P09-71 will enter extension mode.
Note: The value of P09-70 is the address of C2000 in DeviceNet. The address has to be consistent with the address of
C2000 during configuration. Changing the value in P09-70 when C2000 is working will be invalid. After the value in P09-70 is changed, please shut down C2000 and re-power it to make the parameter valid.
Constructing DeviceNet Network
DVPDNET-SL is the DeviceNet master, and CMC-DN01 and C2000 construct DeviceNet slave. Use DeviceNet Builder software to configure the DeviceNet network.
Controlling and Using the I/O on an AC Motor Drive by a Communication Card
1. Controlling the setting by a control card
Multi-function output terminal Parameter
Setting value
*Relay3 is for CP2000. MO1~MO2 are for C2000/CH2000. 2. Control addresses
TerminalAddress
R/W Address length Description Digital inputs b15~b0 Digital outputs b15~b0 2660h
R b15~b0 Percentage of AVI analog input signals AI 2661h
R b15~b0 Percentage of ACI analog input signals AO
26A0h
RW b15~b0 Percentage of AFM1 analog output signals 26A1h
RW b15~b0 Percentage of AFM2 analog output signals
Correspondence for the address 2600:
Number Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10Bit 11Bit 12Bit 13 Bit 14 Bit15 I/O on the
control
panel
EMC-D611A



Correspondence for the address 2640:
Number Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10Bit 11Bit 12Bit 13 Bit 14 Bit15 I/O on the control panel EMC-D42AMO10MO11

EMC-R6AARY10RY11RY12RY13RY14RY15 Disconnecting CMC-DN01 from C2000
After C2000 is shut down, remove the two screws (as Figure 5) to twist open the card clip (as Figure 6). Insert the slot type screwdriver to the hollow and prize the PCB off the card clip. Twist open the other card clip (as Figure 7) to remove the PCB.
[Figure 5]
[Figure 6]
[Figure 7]
[ LED Indicator & Troubleshooting
There are 3 LED indicators on CMC-DN01. POWER LED displays the status of power supply. MS LED and NS LED are dual-color LED, displaying the connection status of the communication and error messages.
POWER LED
LED status Indication
How to correct
On Power supply in abnormal status. Check the power supply of CMC-DN01.
NS LED
LED status
Indication
How to correct
1. Check the power of CMC-DN01 and see if the No power supply or CMC-DN01 has not connection is normal.
Off completed MAC ID test yet.
2. Make sure at least one or more nodes are on the bus. 3. Check if the serial transmission speed of CMC-DN01 is the same as that of other nodes.
Green light CMC-DN01 is on-line but has not 1. Configure CMC-DN01 to the scan list of the master. flashes established connection to the master. 2. Re-download the configured data to the master. Green light on connected to the master
--
Red light CMC-DN01 is on-line, but I/O connection 1. Check if the network connection is normal. flashes
is timed-out.
2. Check if the master operates normally.
1. The communication is down. repeated.
Red light on
2. MAC ID test failure.
2. Check if the network installation is normal.

3. No network power supply. 3. Check if the baud rate of CMC-DN01 is consistent 4. CMC-DN01 is off-line.
with that of other nodes.
4. Check if the node address of CMC-DN01 is illegal. 5. Check if the network power supply is normal.
MS LED
LED status Indication
How to correct
Off No power supply or being off-line Check the power supply of CMC-DN01 and see of the connection is normal.
flashes Waiting for I/O data Switch the master PLC to RUN status Green light on I/O data are normal
--
flashes Mapping error
2. Re-power AC motor drive
Red light on Hardware error
1. See the error code displayed on AC motor drive.
2. Send back to the factory for repair if necessary.
Orange light CMC-DN01 is establishing connection with
flashes
AC motor drive.
and AC motor drive are correctly installed and normally
connected to each other.
注意事項
3 此安裝手冊只提供電氣規格、一般規格、安裝及配線等。 3 配線時請務必關閉電源,請勿在上電時觸摸任何端子。
3 本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊∕
衝擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開),防止非維護人員操作或意外衝擊本體,造成危險及損壞。
3 輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。
3 交流輸入電源不可連接於輸入∕輸出信號端,否則可能造成嚴重損壞。請在上電前再次確認電源配線,且請
勿在上電時觸摸任何端子。本體上的接地端子
務必正確的接地,以提高產品抗干擾能力。
X 產品簡介!
感謝您使用台達CMC-DN01網路通訊卡。CMC-DN01定義為DeviceNet網路通訊卡,用於將台達C2000、CH2000、CP2000、CT2000及AFE2000系列交流馬達驅動器接入DeviceNet網路。
功能特色
1. 基於台達HSSP協定的高速通訊介面,可對交流馬達驅動器進行即時控制。 2. 支援Group 2 only連接方式,支援輪詢I/O資料交換。 3. I/O映射最大支持32字輸入,32字輸出。
4.
支援在DeviceNet配置工具軟體裡使用EDS檔進行配置
5.
支援DeviceNet匯流排的所有通訊速率:125kbps、250kbps、500kbps及擴充串列傳輸速率模式。 6. 通訊站號和串列傳輸速率可直接在交流馬達驅動器上設定 7.
通訊卡可自動從交流馬達驅動器獲得工作電源
產品外觀
[圖1]
1. NS指示燈 2. MS指示燈 3. POWER指示燈 4. 通訊卡定位孔 5. DeviceNet連接埠 6. 螺絲固定孔 7. 通訊卡防呆溝槽 8. 交流馬達驅動器連接埠
Y 功能規格
DeviceNet連接埠
接頭

5針開放式可插拔連接頭,腳位間隔5.08mm 傳輸方式
CAN
傳輸電纜
遮罩式雙絞線(帶兩條電源線)
傳輸速率、250kbps、500kbps及擴展串列傳輸速率模式 網路協議協議
交流馬達驅動器連接埠
接頭PIN通訊端子 傳輸方式通訊 端子功能 1. 通訊卡通過該介面與交流馬達驅動器通訊 2. 交流馬達驅動器通過該介面給通訊卡提供電源 通訊協議
台達HSSP協議
電氣規格
電源電壓(由交流馬達驅動器提供) 絕緣電壓
500VDC 通訊線電力消耗 0.85W 電力消耗 1W 重量
23g
環境規格
ESD (IEC 61800-5-1,IEC 6100-4-2) 雜訊免疫力
EFT (IEC 61800-5-1,IEC 6100-4-4)
Surge Teat(IEC 61800-5-1,IEC 6100-4-5)
Conducted Susceptibility Test(IEC 61800-5-1,IEC 6100-4-6) 操作∕儲存環境 操作:-10°C ~ 50°C(溫度),90%(濕度) 儲存:-25°C ~ 70°C(溫度),95%(濕度)
耐震動∕衝擊
國際標準規範IEC61131-2, IEC68-2-6 (TEST Fc) / IEC61131-2 & IEC 68-2-27(TEST Ea)
Z 安裝
註:以下內容僅以C2000示意。
DeviceNet連接埠腳位定義
腳 位
訊 號
顏 色
敘 述 紅色 DC24V
白色 正信號線 接地線 藍色 負信號線 黑色
0V
HttpWatch安装及使用说明_IT/计算机_专业资料。HttpWatch安装及使用说明工具简介使用技巧( HttpWatch 工具简介-HttpWatch 使用技巧(一) 一 概述: 概述:强大的网页...
Zebra Designer 中文操作手册 条码软件使用操作手册(Zebra Designer) 1 Zebra Designer 中文操作手册 Zebra Designer 使用说明软件的安装及运行 中文打印 一、软件的...
中联和安装步骤说明安装前的要求工作:D 盘安装数据库,E 盘备份数据库(备份计 划) 盘使用工具存放路径。 ,F 安装前的准备工作:oracle10g 安装文件,ZLBase10.25....
A6BD汽车行驶记录仪使用及安装说明中性_交通运输_工程科技_专业资料。道路运输车辆卫星定位系统车载终端 A6BD 北斗汽车行驶记录仪 用户使用手册 (V1.1) 一、 ...
移动办公安装和使用说明 1 目录 第一部分 第二部分 安装操作使用操作 2 目录 第一部分 安装操作 3 安装操作-iPhone手机安装 ? 下载91手机助手 可以在网上搜索...
雕刻机安装说明书_计算机硬件及网络_IT/计算机_专业资料。前 言: 感谢您选购***系列 CNC 雕刻机。 本使用说明书为随机技术文件。是您正确使用,安全运 行雕刻...
ZTHCAM160 快速安装指南v1.1_电子/电路_工程科技_专业资料。ZTHCAM 160安装说明及连线指南版本:1.1 日期:2013年8月 1、注意事项请注意以下安全事项,误操作可能...
CAD安装说明_计算机硬件及网络_IT/计算机_专业资料。cad2014 是一款由 Autodesk 公司设计制作的 AutoCAD 系列图像制作处理软件。AutoCAD 2014 相比 autocad 2013 ...
罐下采样器安装说明_机械/仪表_工程科技_专业资料 暂无评价0人阅读0次下载举报文档 罐下采样器安装说明_机械/仪表_工程科技_专业资料。罐下采样器安装操作...
家用无线路由器安装方法全程图解_IT/计算机_专业资料。路由器的安装方法,比较实用家用无线路由器安装方法全程图解在家庭或小型办公室网络中,通常是直接采用无线路由...
热门文档