Design and Operation of Fan-Coil Units in Using River-Water as chilled water

自然低温水空调风机盘管设计

Design and Operation of Fan-Coil Units in Using River Water as Chilled Water

Aihua Jiang Huihe Chen Weiwu Ma Associate Professor Master Doctor School of Energy Science and Engineering, Central

South University

Changsha, Hunan Province, China

jah65@163.com

Abstract: Based on the case research for China’s first central air conditioning system utilizing natural cool river water as chilled water, this paper analyzes the technical design-and-innovation process and operating characteristics of Fan-Coil Units (FCUs) in the system. An approximate formula is proposed for computing the cooling capacity of FCUs when the temperature of water supply is a little higher than designed temperature. Finally, recommendations are given for the design of the FCUs to follow dry operating conditions in the air conditioning system that directly utilize natural cool resources.

Key words: natural cool resource;Fan-Coil Units (FCUs);temperature of water supply;dry operating condition

Hanwen Zhu Manager

Liyujiang Ltd., Hunan Huarun

Electricity Power

Chenzhou, Hunan Province, China

1. INTRODUCTION

As an indispensable terminal equipment in semi-concentrated air-conditioning system, the FCUs are mainly used to exchange cool or thermal energy with indoor air of rooms. The cooling or thermal capacity of FCUs is influenced by many factors such as the temperature and the flux of medium, the velocity of air passing FCU transversely and the properties of indoor-air, and so on. Especially, the temperature of inlet-water can not only make a strong impact on the capacity of the energy afforded by FCUs, but also affect the economic capability of the whole air-conditioning system directly.

As a rule, the designers of A/C systems pay more attention to the design of the inlet-water temperature of FCUs, and many correlative criteria have been established. Generally, considering the economic benefit of an air-conditioning system wholly, it is advisable that the inlet-water

temperature of FCUs should not be higher than 7 , so the designing parameter of the inlet-water temperature provided by many air-conditioning manufactories is just 7 or not more than 10 . However, for these air-conditioning systems using natural river-water or well-water as cooling resource, the inlet-water temperature is often higher, even up to 15 , and the data provided by many air-conditioning manufactories do not suit the design of this kind of air conditioning systems. So, it is necessary to develop a suited and usable method to calculate and design such systems. The concentrated air-conditioning system, which came into use in 2000, in Liyujiang Power Plant, utilizes the discharged water of the Dongjiang reservoir as water supply of the FCUs directly, and the inlet-water temperature is about 14 . Testified by the successful operation of this A/C system, that the A/C systems direct-utilizing natural cool river-water as chilled water needn’t refrigeration equipments and is not only a system with superexcellent economic benefit, but also a green and energy-saving air-conditioning system with environmental benefit, and is very worthy of extending. Therefore, for popularizing such an A/C system, energy-saving and protecting environment, it is of very significance to research the design approaches and operation performance of the FCUs with higher inlet-water temperature.

2. DESIGN OF FCUS IN A/C SYSTEMS DIRECT-USING COOL RIVER-WATER

2.1 Characteristics of Water Systems in the A/C System Direct-Using Natural Cool Resource

The air-conditioning system built in Liyujiang