文档下载 文档下载导航
设为首页 | 加入收藏
搜索 请输入内容:  
 导航当前位置: 文档下载 > 所有分类 > 工程科技 > 能源/化工 > 智能变电站保护配置方案研究
侵权投诉

智能变电站保护配置方案研究

智能变电站保护配置

第40卷 第1期 电力系统保护与控制 Vol.40 No.1 2012年1月1日 Power System Protection and Control Jan. 1, 2012

智能变电站保护配置方案研究

高东学1,智全中1 ,朱丽均2,梁 旭3

(1.漯河供电公司,河南 漯河462000; 2. 浙江省丽水电业局,浙江 丽水 323000; 3.清华大学电力系统及发电设备安全控制和仿真国家重点实验室,北京 100084)

摘要:根据典型三层两网智能变电站的特点,提出了基于分层配置的继电保护方案设计,线路保护、变压器保护等间隔保护安排在过程层,不依赖过程层交换机独立跳闸。多间隔的母线保护配置在间隔层,通过过程层交换机网络实现保护和跳闸。设计了站域智能保护管理单元,配置在站控层,实现站域(后备)保护和管理。线路保护和变压器只含包含传统保护中的主保护,其他后备保护由站域智能保护单元实现。该设计将全局信息引入继电保护系统,重新审视保护的原理与配置,即能保证主保护基本不受系统运行方式的影响,可快速切除故障元件,又可解决后备保护易受系统运行方式影响,配合关系复杂,动作时间长等问题,为我国电网铸造更加安全、可靠的第一道防线。 关键词: 智能变电站;主保护;后备保护; 全景数据;IEC6l850

Configuration project of protect unit according to levels for smart substation

GAO Dong-xue 1 , ZHI Quan-zhong1 , ZHU Li-jun2, LIANG Xu3

(1. Luohe Power Supply Company, Luohe 462000,China; 2. Zhejiang Provincical Lishui Electric Power Bureau,

Lishui 323000, China; 3. State Key Laboratory of Control and Simulation of Power System and

Generation Equipments, Tsinghua University, Beijing 100084, China)

Abstract: According to the characteristic of the typical smart substation communication architecture of three levels & two networks, this paper gives a configuration project of protect unit according to levels, and the interval protection such as line protection and transformer protection are arranged at the process level, whose trip does not rely on the digital switching system. Busbar protection is arranged at the bay level, whose protection function and trip depend on the digital switching system. A smart cell of protection and management is designed and configured at substation level to carry out all the back-up protection and run of substation. Line protection and transformer protection reserve the function of main protection, and smart cell of substation area accomplishes all the back-up protection. The scheme has panoramic data of all substation, and configures the function of protection over again, i.e. it can ensure that the main protection is not affected by system operation mode, can cut off fault component rapidly of the main protection, and also can solve the problems that the backup protection is influenced by system operation mode easily, configuration relationship is complex, operation time is long, etc., which constructs the safe and reliable first defense line of power systems of China. Key words: smart substation;main protection;back-up protection;panoramic data; IEC6l850 中图分类号: TM77 文献标识码:A 文章编号: 1674-3415(2012)01-0068-04

0 引言

为了实现智能(数字化)变电站的功能,需要对变电站内部智能电子设备(例如继电保护、测控装置等)的信息描述方法、访问方法、通信网络等进行统一规范。IEC61850为数字化变电站提供了一套完整的信息描述和访问规范,使得不同厂家的智能电子设备具有互操作性。在中国,正在建设或已经运行的智能变电站,无一例外的采用IEC61850

通信规约[1-2]。

IEC61850标准通过对变电站内网络通信进行抽象,把变电站分为站控层、间隔层和过程层三层。图1给出了一个典型的“三层两网”模式的示意图,保护装置和监控装置处于间隔层。

目前,智能(数字化)变电站保护配置方案和采用常规互感器时一样,保护装置按对象进行配置,如主变保护、线路保护、母线保护、开关保护等。只不过将原来保护装置的交流量输入插件更换为数