Design of robust control and monitoring system for microgrid stabilization
damping effect of the PMT & PES is higher than the PES and PMT. Also, the tie line power fluctuation with interconnected utility grid operation is shown in Fig.9. The tie line power deviation of the PMT & PES is lower than the PES and PMT. These confirm the well coordinated control of Finally, in the case of the interconnected utility grid operation, it is supposed that MG system under the WP, PV and FC outputs and random load change as shown in Figs.6-7 is unstable since D is changed from 1 to -0.265 (negative damping), KES and M are decreased by 30%, TES, the PMT & PES in RCMS.
Figure 6. The WP, PV and FC outputs.

Figure 7. Random load change.

Figure 8. Frequency deviation with islanding operation.

Figure 9. Tie line power deviation with interconnected utility grid operation.
In the case of the changed system parameters, it is assumed that the system operated in the islanding mode under the WP, PV and FC outputs and random load change
in Figs.6-7 becomes unstable when D is changed from 1 to -0.1 (negative damping), KES and M are decreased by 30%, TES and KMT are increased by 30% from the normal values. Simulation result of the frequency deviation is shown
in Fig.10. As seen in Fig.10, the PMT & PES can damp
effectively. On the other hand, the CMT & CES fails to suppress the frequency deviation in system. KMT and Xtie are increased by 30% from the normal values. The deviation of tie line power is shown in Fig.11. Clearly, the tie line power oscillation of the CMT & CES completely loses the damping characteristic. In contrast, the PMT & PES is extremely robust against the system parameters variation. This result implies the superior robustness of the proposed

RCMS.
Figure 10. Frequency deviation (changed system parameters).

Figure 11. Tie line power deviation (changed system parameters).
V. CONCLUSION
In this paper, a practical design of RCMS for MG stabilization has been presented. The PSO-based fixed-structure H∞ loop shaping control is proposed to concurrently optimize the PI controller parameters of MT and ES in both islanding and interconnected utility grid operations. The designed PI controller is very robust against system operations and easy to implement in real system. Simulation results confirm the well coordinated control and the robustness of the proposed RCMS under various conditions.
ACKNOWLEDGMENT
This work was supported by the King Mongkut's Institute of Technology Ladkrabang Research Fund.
REFERENCES
[1] B. Kroposki, R. Lasseter, T. Lse, S. Morozumi, S. Papathanassiou and N.
Hatziargyriou,“Making Microgrids Work,” IEEE Power and Energy
Magazine, Vol.6, Issue.3, pp.40-53, 2008.
[2] X. Li, Y.J. Song and S.B. Han,“Study on Power Quality Control in
Multiple Renewable Energy Hybrid MicroGrid System,” IEEE International Conference Power Tech, pp.2000-2005, 2007.
[3] X. Li, Y.J. Song and S.B. Han,“Frequency control in micro-grid power
system combined with electrolyzer system and fuzzy PI controller,” International Journal of Power Sources, pp.468-475, 2008.
[4] J. Kennedy and R. Eberhart,“Particle swarm optimization,” in Proc. IEEE Inter. Conference Neural Networks, Vol.1, pp.1942–1948, 1995.
[5] D.C. Mcfarlane and K. Glover, Robust controller design using
normalized coprime factor plant descriptions. Lecture Notes in Control and Information Sciences, Springer-Verlag, Berlin, Vo1.138, 1990.
System for Frequency Control in Microgrid System K...stabilization from the battery system, PRR is ...V. THE CONTROLLER DESIGN OF THE BATTERY ENERGY ...
16 Design of Robust Power System Stabilizer in ...effective machines for stabilization have been ...Despite the significant potential of control ...
Robust stabilization and disturbance attenuation for a class of underactuated mechanical system_专业资料。JCetSuhUi.21)928—45.n.ot nv(021:4829 DoI010/l...
A robust control approach to stabilization of ...The stochastic system approach may not be ...(2004). State feedback controller design of ...
The Status of DC microgrid protection_电力/水利... allowing for a more robust de-centralized ...Protective System Design It has long been ...
for Isolated Power System Stabilization Eitaro Omine...enables intuitive controller design in frequency ...control, frequency control, H∞ control, microgrid...
Such a design problem is referred to as semi-global practical stabilization ...International Journal of Robust and Nonlinear Control 1995; 5:375–380. 2....
Design of system protection philosophy with a ... monitoring and control of all microgrid assets ...stabilization, as well as other ancillary system ...
Such a design problem is referred to as semi-global practical stabilization ...International Journal of Robust and Nonlinear Control 1995; 5:375–380. 2....
热门文档