勤丰变电站10 kV电容器组常发生熔断丝烧断而保护不动作的故障。通过对原电压保护进行原理分析和计算分析,提出电容器电压保护定值整定的思路:增加不平衡电压保护的灵敏度;对过电压保护的整定值进行明确。

doc.guandang.net

参考文献

[1]坦尾变电站10kV电容器电压保护改造的原理分析,广东电力,2004年03期 [2]DSA保护监控一体化系统技术说明书(V2.00),南瑞城乡 [3]3~110kV电网继电保护装置运行整定规程,DL/T 584-95 [4]变电运行技术问答,华北电业管理局,1997.6

Theoretical analysis on voltage protection setting for

10kV condenser bank in Qinfeng Substation

1

Shi Weiqing 1 Tan Taiyang

1

ChuXiong Bureau,Yunnan power grid Corporation, chuxiong 675000,Yunnan Province,China

ABSTRACT

The protection for 10 kV condenser bank in Chuxiong Substation often fails to operate because of fuse burn out A resultant theoretical and computational analysis is made on the original voltage protection Some measures for improvement are put forward, which include modifying the connection scheme of the unbalanced voltage protection as well as adjusting the setting values of the over voltage and under voltage protection.

KEY WORDS: substation; condenser; voltage protection; setting calculation