Effects of non-uniform refrigerant and air flow

空调

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned-Tube Evaporator Performance

Jong Min Choi, W. Vance Payne and Piotr A. Domanski

National Institute of Standards and Technology

Building Environment Division MS 8631, Building 226, Room B114 Gaithersburg, Maryland USA 20899

Phone: 301-975-6663 Fax: 301-975-8973 Email: vance.payne@nist.gov

ABSTRACT

An experimental investigation was implemented to determine the capacity degradation due to non-uniform refrigerant and air flow distributions, and to assess the potential to recover the lost capacity via controlling refrigerant distribution between individual refrigerant circuits. The tests were performed on a three-circuit, three-depth-row, finned-tube evaporator. Refrigerant inlet quality, exit saturation temperature, and exit superheats for the individual circuits were controlled.

The study showed that capacity degradation due to refrigerant maldistribution can be as much as 30 %, even when the overall evaporator superheat is kept at the target 5.6 ºC. Experimental data indicate that part of this capacity degradation was caused by the internal heat transfer within the evaporator assembly. For the coil and air maldistributions studied, the maximum capacity degradation was found to be 8.7 %. A 4.0% capacity recovery was obtained by controlling refrigerant distribution to obtain the target 5.6 ºC at each circuit exit.

INTRODUCTION

Most evaporators use an inlet expansion valve with a flow distributor to control the overall superheat at the evaporator exit manifold. In the evaporator, the refrigerant flows through parallel refrigerant circuits, which are designed to optimize between the benefit of improved refrigerant heat transfer and the penalty of refrigerant pressure drop. The coil performs optimally when the superheat at individual circuit exits matches the desired overall superheat in the exit manifold.

Evaporator air velocities may vary due to the geometry of the heat exchanger installation, nearness of the blower, blockage of the air filter, and other factors. Non-uniform air flow can cause some circuits to have excessive superheat while others may remain two-phase at the evaporator exit. In such situations, some circuits inefficiently use coil area when transferring heat with superheated vapor instead of two-phase refrigerant.

Liang et al. (2001) conducted a numerical study of an evaporator with various refrigerant circuits operating with uniform air flow. The researchers found that using a complex, optimized refrigerant circuit arrangement with refrigerant circuits properly branched may reduce the needed heat transfer area by about 5 % for the same capacity. Kirby et al. (1998) experimentally investigated the performance of a 5275 W window air conditioner under wet and dry coil conditions with non-uniform air flow over the evaporator. The velocity variation over the evaporator varied by a factor of 3, but upon correcting the non-uniformity of air flow, the investigators saw only a minor improvement in performance. Chwalowski et al. (1989) performed a simulation and experimental study of an evaporator operating with five different air velocities cause by different installations. In the extreme case, they reported a capacity difference of 30 %. Lee et al. (1997) executed a simulation study of an R22 and R407C evaporator with non-uniform air and refrigerant distributions. The study showed that the level of capacity degradation is affected by the refrigerant circuitry design and air velocity profile relative to that circuit. For the cases studied, they reported that the capacity of the evaporator showed a greater sensitivity to air maldistribution than to refrigerant maldistribution.