Temperature & Altitude Effectson Fans

Introduction

Fans are tested in laboratories with test setups that simulate installations that are typical for that type of fan. Usually they are tested and rated as one of four stan-dard installation types as designated in AMCA Standard 210. These standard installation types are shown in Figure 1.

Figure 1. Standard Fan Installation TypesTemperature EffectAny temperature other than 70°F affects the air/gas density. Fan pressure (P) and horsepower (H) vary directly with the ratio of the air/gas density at the fan inlet to the standard density; however, fan air volume (CFM) is not affected by the air density. Fans are con-stant volume machines that, when operating at constant speed will deliver the same CFM at 0.075 lb/ft3 density air as they will with lower density air or higher density air. For example, Figure 2 illustrates the effect on the fan performance of a density variation from the standard value created by a change in fan inlet temperature.

Figure 2. Percent of Duct/Fan System Airflow – Q

Products that are rated and certified by AMCA must illustrate that they have been rated by one of the instal-lation types shown above. In addition to listing the test type, the ratings must also be published at a standard air inlet density. The fan industry has adopted a standard density of 0.075 lb/ft3 at 70°F at sea level and at a barometric pressure of 29.92" Hg. All manufacturers’ ratings are made at, or adjusted to, this standard. Whenever a fan is operated in a system where any or all of these conditions vary, corrections must be made in order to obtain accurate results. It’s not enough to make fan performance adjustments based on density corrections. The designer must also consider what effect the variables that are influencing the fan air density might have on the structural compo-nents of the fan. Temperatures other than 70°F can cause an alloy to become too pliable or brittle. Speed adjustments can exceed the limits of the wheel, shaft and bearings. Gases, other than air, that change the inlet density may also be corrosive to vital structural components. All these variables must be considered when making fan inlet density adjustments. This density ratio must always be considered when selecting a fan from a manufacturer’s catalogs or curves. The dashed curve is representative of cataloged fan performance at 70°F at sea level with a barometric pres-sure of 29.92" Hg. (standard air). The solid curve is representative of the fan’s performance with an inlet temperature of 600°F at the same altitude and baromet-ric pressure. The fan laws, with the size and speed remaining constant, that apply here are as follows:Where: Q = CFM (cubic feet of air per minute)Qc = Q P = pressure (inches of water)Pc = P (ρc/ρ) H = fan brake horsepowerHc = H (ρc/ρ) ρ = air density (pounds per cubic foot) subscript c = converted valueρc/ρ = density ratio

©2001 Clarage