Comparison of Front-End Power Supplies to Rectifier Modules

开关电源设计

Comparison of Front-End Power Supplies to Rectifier Modules

Introduction

How does a front-end power supply differ from a rectifier module? Though similar, there are subtle differences between these two kinds of power supplies, and these differences need to be understood before the most-appropriate power system can be configured.

Front-End Power Solutions

The input of a front-end is connected to an AC voltage, and its output is a regulated DC bus voltage. This bus voltage, commonly 12V, 24V, or 48V is typically used to power other DC-DC converters; however, it’s important to note that front-ends should not be used in applications where batteries are to be charged and monitored. Batteries require sophisticated charging circuitry, and front-end supplies do not have this capability.

Markets Served by Front-Ends Networking equipment/datacom

Enclosures / Cabinet power Data storage Data Centers

Blade Servers

The AC input voltage range for a front-end is typically from 87 VAC to 264 VAC, and front-ends will usually be powered from a single-phase input. Some front-ends can be operated from a DC source; however, the AC input version is much more common. The connection to the AC input voltage is usually located at one end of the power supply chassis, while the connection for the output DC bus voltage is located at the opposite end of the power supply. The AC input connector, e.g., an IEC-type AC plug, is usually located at the front of the supply, and the DC output is located at the rear. Power–One also offers a family of AC front-ends whose input and output connectors are located on the same end.

The typical output power rating of an individual front-end ranges from 300 watts to 1800 watts. Cooling is provided by internal fans, and the direction of airflow is usually from front-to-rear, although models with reverse airflow are available. All front-end supplies from Power-One incorporate internal ORing FETs and employ a droop method technique for current sharing.

Power-One FNP1800, 1800-Watt Front-End

Front-ends are often mounted into a power shelf, such as the one shown below, that accommodates more than one front-end when additional or redundant power is needed.

Power-One's FNR-3 Shelf provides up to 5400 Watts in a 1U-High, 19" Rack

The typical operating ambient temperature range of a front-end is 0 to 50 ºC. These supplies can be operated in ambient temperatures exceeding 50 ºC; however, the output power will usually begin to derate above 50 ºC. The maximum operating temp-erature for front-ends is usually 70 ºC., and the common derating from 50 ºC. to 70 ºC. is 2.5% / ºC, such that the supply will provide 50% of its rated output current at 70 ºC.

Status information is provided from the front panel LEDs, logic signals, and via the I2C management interface. The I2C bus can also enable the power supply, control fan speed, and adjust the output voltage. Status LEDs give indications of the input voltage, the output voltage, and the presence of an overtemperature condition.

Rectifier Modules in a DC Power System

A typical DC Power System is comprised of a minimum of four components: rectifier modules, a controller/supervision module, and distribution modules mounted in one or more power shelves. Batteries are often part of a DC Power System, as well. Rectifier modules are similar to front-ends, but there are important differences. Perhaps the most notable difference is that rectifier modules, when used in conjunction with a controller/supervisor module, provide sophisticated battery management to adjust their output voltage as required for charging batteries. In general, a rectifier module and assoc-iated power system could be used in a front-end application, but a front-end could not be used in a DC Power System application that requires battery management.

The AC input and DC output connectors are both located at the rear of a rectifier module. The rectifier module’s regulated output bus voltage is typically +24 VDC (27.25 VDC float voltage), or -48 VDC (-54.5 VDC float voltage), with -48 VDC being the most prevalent. Rectifier module cooling is usually provided by internal fans, and the airflow direction is

Comparison of Front-End Power Supplies to Rectifier Modules

Comparison of Front-End Power Supplies to Rectifier Modules

Comparison of Front-End Power Supplies to Rectifier Modules

Comparison of Front-End Power Supplies to Rectifier Modules

Comparison of Front-End Power Supplies to Rectifier Modules

typically from front to rear. Natural convention-cooled