SOLAS - Structural Fire Protection - Interpretation

General Guidance – Interpretations

Drawings are to be reviewed in accordance with their applicable requirements. The following are interpretations used in the drawing review process:

NOTE: The following does not represent all interpretations, but rather highlights the interpretations used frequently in the past. Also, refer to FSS Code, FTP Code, IMO MSC/Circ.847, (refer to IMO MSC/Circ.1120 for fire protection construction, installation, arrangements and equipment installed on board ships on or after 1 July 2004,) and additional IACS Interpretations and ABS-developed I/Is pertaining to the subject.

1) Reg. 3.1: Pantries or isolated pantries containing no cooking appliances

(MSC/Circ.847)

Pantries or isolated pantries containing no cooking appliance may contain: coffee automates, toasters, dishwashers, microwave ovens, water boilers and similar

appliances each of them with a maximum power of 5 kW;

electrically heated cooking plates and hot plates for keeping food warm, each of them with a

maximum power of 2 kW and a surface temperature not above 150oC.

A dining room containing such appliances should not be regarded as a pantry.

2) Reg. 3.18: Control stations (IMO MSC/Circ.847)

Main navigational equipment includes, in particular, the steering stand and the compass, radar and direction-finding equipment.

Steering gear rooms containing an emergency steering position are not considered to be control stations.

In the regulations of chapter II-2 relevant to fixed fire-extinguishing systems where there are no specific requirements for the centralization within a control station of major components of a system, such major components may be placed in spaces which are not considered to be a control station.

Spaces containing the following battery sources should be regarded as control stations regardless of battery capacity:

1) emergency batteries in separate battery room for power supply from black-out till start

of emergency generator,

2) emergency batteries in separate battery room as reserve source of energy to

radiotelegraph installation,

3) batteries for start of emergency generator, and 4) all emergency batteries required in pursuance of Reg.II-1/42 or Reg.II-1/43.

3) Reg. 3.45: Devices in main pantries, pantries containing cooking appliances and galleys

(IMO MSC/CIRC.847)

Main pantries and pantries containing cooking appliances may contain:

coffee automates, toasters, dishwashers, microwave ovens, water boilers and similar appliances each of them with a power of more than 5 kW,

electrically heated cooking plates and hot plates for keeping food warm, each of them with a maximum power of 5 kW.

Spaces containing any electrically heated cooking plate or hot plate for keeping food warm with a power of more than 5 kW should be regarded as a galley.

4) Reg. 4.4.4 & Reg. 6.3: Restricted use of combustible materials

(ABS interpretation)

Surface materials used only for small areas of application such as combustible molding and skirting for decorative purpose may not be required to comply with Reg. 4.4.4 and Reg. 6.3.

SOLAS – Structural Fire Protection,