a novel current regulated PWM technique for multi-converter active power line conditioner

A Novel Current Regulated PWM Technique for Multi-Converter Active Power Line Conditioner

M. I. Marei, E. F. El-Saadany and M. M. A. Salama

Electrical and Computer Engineering Dept. University of Waterloo, Ontario, Canada

A quick response, easy implementation, maximum current capability and insensitivity to line parameters variation are among the important features of any current controller. A three independent HCC’s is a rather popular topology. Yet, due to the lack of coordination between the individual HCC’s of the three phases, high switching frequency may arise and current error is not firmly limited. Some hysteresis current controller techniques applying a zero vector procedure in order to reduce the number of switching were reported in the literature [11-13].

However, these techniques require some knowledge about the inverter terminal voltage [11] or it does not show how to determine a set of space vectors including the zero vector to reduce the number of switching [12,13]. If some

information of the derivative of the current error were Index Terms— Harmonic distortion, Space vector modulation

SVM, HCC, Active filters, Distribution systems. available, then one would know the changing tendency of the current error. Hence, the HCC can be utilized in order

I. INTRODUCTION to force the output current vector to track the command

vector with almost negligible response time and

tilization of non-linear devices and static power insensitivity to line voltage and line parameter variations. converters have been a common practice in the last The HCC generates other vectors apart from the space two decades leading to serious concerns regarding vectors required according to the region in the SVM distribution systems power quality. Those converters are technique. If a zero vector is applied to reduce the employed at different power levels’, ranging from large magnitude of the output current vector, the line current can adjustable speed drives to small power supplies for office be decreased with sluggish slope and thus, the switching equipment and computers. The typical harmonic currents frequency can be decreased. The utilization of nonzero injected by these types of loads into the distribution system vectors instead of a zero vector in decreasing the output are mainly odd harmonics and laying between the third and current leads to an increase in the switching frequency. eleventh harmonics in large quantities and other higher Therefore, the SVM based HCC topology is aimed to frequency harmonics in smaller percentages. Active power utilize all the combined features of both HCC and SVM filters APF have been suggested as an effective, dynamic techniques [14].

and practical solution for harmonic elimination [1-6]. In this paper, a multi-converters active power line However, the ability of a converter to perform effectively conditioer constructed from CRPWM inverters controlled by SVM based HCC is proposed. This active filter distribution of the distortion for which it must compensate. topology reduces significantly the switching frequency. The performance of the proposed system is simulated using APF controller consists of two main parts [7,8]; the first Matlab, Simulink and C++ programing. The results are usually measures the load current and resolve the reference discused to demonstrate the potent of the proposed harmonic current by filtering out the fundamental technique. component. The second part standardizes the generation of the appropriate gating patterns of the inverter switches in II. PROPOSED APF CONFIGURATION order to maintain continuous tracking of the reference

current. Consequently, the APF injects proper Figure 1 shows the fundamental building block of a compensation current, resulting in a sinusoidal current modular APF connected to a distribution network. Each waveform being drawn from the point of common coupling module is assembled of a standard three-phase IGBT PCC. inverter bridge with input AC inductance Lh, resistance Rh

The current controller symbolizes a vital bone in and a DC capacitor Ch. Each module is tuned to mitigate a CRPWM inverters. It should be able to force the APF current to follow the reference current as quickly as possible and grantee the controller requirements. Various depends on the magnitude of the harmonic current to be current controller strategies have been developed [9-12]. mitigated by that unit.

Abstract: This paper presents a multi-converter (modular) active power filter for high power nonlinear loads harmonic mitigation. The proposed system comprises of a Current Regulated Pulse Width Modulation inverter (CRPWM) modules that are utilizing a novel space vector modulation (SVM) based hysteresis current controller (HCC). The proposed methodology exploits the combined advantages of both HCC and SVM techniques. A set of space vectors including the zero vector, to reduce the number of switching, is determined from two sets of hysteresis comparators. One comparator set has larger hysteresis band than the other set. As a result, the proposed system significantly reduces the number of switching and, therefore, increases the efficiency of the power electronics modules.

0-7803-7322-7/02/$17.00 © 2002 IEEE