Studies of Elastic Waves Caused by Corona

IEEE Transactions on Dielectrics and Electrical Insulation

Vol. 6 No. 6, December 1999

825

Studies of Elastic Waves Caused by Corona Discharges in Oil T. Sakoda, T. Arita, H. Nieda Department of Electrical Engineering Kumamoto Institute of Technology, Japan

K. Ando Center for Cooperative Research Kyushu Institute of Technology, Japan

M. Otsub and C. Honda Department of Electrical and Electronic Engineering Miyazaki University, Japan

ABSTRACT In order to diagnose the deterioration of insulation and evaluate its location in oil-filled pole transformers, measurements of elastic waves brought by corona discharges in oil were performed, based on an accoustic emission (AE) technique. The detected signals in these measurements were analyzed by means of a fast Fourier transform (FFT) and their properties were discussed theoretically, It was found that the A E signals due to the Lamb waves of symmetric mode caused in a thin steel tank could be recognized easily by the FFT analysis of initial stages of the detected AE signals. This suggests that the accuracy on location of the AE sources in the transformer would be improved. Also, it was shown that a low pass filter was effective in improving the location accuracy.

1

INTRODUCTION

stopping the apparatus.

Furthermore, if the position of discharge in the transformer can be evaluated correctly, effectivelywe can prevent the dielectric breakdown. Placing several AE sensors in a 3-dimensional space, the AE technique would be used to locate the position of discharge in the apparatus by using the velocities of the detected elastic waves and their transmission times. However, an evaluation of the correct location of the disOn oil-filled pole transformers for power distribution systems, the charge in the pole transformer is difficult to accomplish, because acousmeasurement of increased leakage current or detection of produced tic emissions due to the discharge proceed in all directions inside the gases has been made into diagnostic techniques of the insulation deteritank, with repeated reflections, transmission and interference. In this oration. However, these examinations are almost never performed uncase, for example, the existent primary wave ( P wave) and secondary der operating conditions. Therefore, it has been attempted to diagnose wave ( S wave) in a cylinder type, thin steel, tank are mutually coupled the insulation deterioration by using an AE technique[I, 21. The AE conand generate a Lamb wave[3,4]. Because then velocities are different, sists of sound and ultrasonic waves as elastic waves and can be observed a calculation error in the location of the discharge position will result. when stress or energy is released in a material. The AE technique is to By this reason, it is necessary to clarify in detail the characteristics of the analyze the AE signals detected by the AE sensor set on the surface of detected AE signals for correct location. a test material. In general, the first AE wave in t

he case of transformIn this paper, as a basic study, we measured elastic waves caused by a ers is radiated in oil with a partial discharge (PD) or a corona discharge, and the induced AE waves are detected on the outside wall of the trans- single pulse corona in oil, based on the AE technique. The results of these former. From the analysis of these detected AE signals, it is possible to measurements were analyzed by means of a FFT in order to understand find the occurrence of discharges under operating conditions. Thus, the properties of the elastic waves and distinguish the kinds of detectable AE technique can be applied as an effective method to diagnose the in- elastic waves. Based on this analysis, we discussed how to improve the sulation deterioration of an apparatus in the system in real time without accuracy of location of PD in the transformer. NY deterioration of insulation in a power system should not be permitted, considering the latest development of information engineering in society. In addition, it is strongly demanded that the diagnostic method of insulation deterioration can be applied even to the system in operation.