RADIANT COOLING RESEARCH SCOPING STUDY

The objective of this project is to characterize the opportunities and limitations of radiant cooling strategies for North America and identify research needs that CBE might most effectively address. Based on literature, case studies, and interviews with e

INTERNAL REPORT APRIL 2006

RADIANT COOLING RESEARCH SCOPING STUDY

RADIANT COOLING RESEARCH SCOPING STUDY

Timothy Moore, Fred Bauman, and Charlie Huizenga

Center for the Built Environment (CBE)

University of California, Berkeley

April 20, 2006

1. BACKGROUND 1.1 OBJECTIVE

The objective of this project is to characterize the opportunities and limitations of radiant cooling strategies for North America and identify research needs that CBE might most effectively address. Based on literature, case studies, and interviews with experienced designers, CBE has set out to determine the focus of radiant cooling research that will best address shortcomings of industry resources and thus provide the most benefit to CBE partners. 1.2 RADIANT COOLING

Radiant cooling uses actively cooled surfaces to absorb excess thermal energy and remove it from a space. This is more or less the inverse of the radiant floor heating systems that have become relatively popular in North American residential applications. In the case of radiant cooling,

thermal energy is flowing from the occupants, equipment, lights, and other surfaces in the room to the actively cooled surface. As long as the cooled surface is at a lower temperature than other surfaces in the room, heat will flow to it from all higher temperature surfaces accessible by line of sight. The radiant exchange itself has negligible effect on air temperature. However, some air in the occupied space is cooled when it comes in contact with the active surface and any other surface indirectly cooled by radiant exchange with the active surface.

Once having been absorbed by the actively cooled surface, heat is removed by water flowing

through a hydronic circuit thermally coupled to the surface. Since there are typically internal latent loads (humidity) from occupants and infiltration, plus sensible and latent loads associated with outside ventilation air, radiant cooling is often part of a hybrid system that includes conditioning of ventilation air to address these loads. In some designs conditioned air provides a significant means of addressing thermal loads in occupied spaces. Many of the potential advantages and challenges related to radiant cooling are associated with the shift toward hydronic systems and away from typical airside systems. Therefore it is important to consider how each of these is affected.