6kV~35kV铜芯、铝芯、交联聚乙烯绝缘电力电缆

· 电缆弯曲半径:三芯电缆不小于电缆外径15倍;单芯电缆不小于电缆外径20倍。

The bending radius of a single-core cable should not less than 20 times of the cable diameter.

The bending radius of a single-core cable should not less than 15 times of the cable diameter.

电缆额定电压的选择 Voltage designation

· 电缆的额定电压应适合于电缆系统的运行状况,用U0/U(Um)kV表示。 U0-电缆设计用的导体对地或金属屏蔽之间的额定工频电压; U-电缆设计用的导体间的额定工频电压; Um-设备可承受的“最高系统电压”的最大值。

The rated voltage of the cable for a given applixation shall be suitable for the operating conditions

in the system in which the cable is used,and is expressed in the form of U0/U(Um)kv Where:

U0-The rated power-frequency voltage between conductors and earth metallic screen ,for which the cable designed;

U - The rated power-frequency voltage between conductos, for which the cable designed; Um- The maximum value of the“highest system voltage”for which the equipment may beused. · 三相系统用电缆的U0值推荐如下表:

he values of U0 recommened for cable to be used in three-phase systems are listed below: